SIPLUS CPU 315F-2 DP производства Siemens

SIPLUS CPU 315F-2 DP
  • For configuring a fail-safe automation system for plants with increased safety requirements
  • Complies with safety requirements up to SIL 3 according to IEC 61508 and up to Cat. 4 according to EN 954-1
  • Distributed fail-safe I/O modules can be connected through the integral PROFIBUS DP interface (PROFIsafe)
  • The fail-safe I/O modules of ET 200M can be also centrally connected
  • The standard modules for non-safety applications can be operated both centrally and locally

Micro Memory Card required for CPU operation.

Note:

SIPLUS extreme products are based on Siemens Industry standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.

 

SIPLUS CPU 315F-2 DP

Order number

6AG1 315-6FF04-2AB0

Order number based on

6ES7 315-6FF04-0AB0

Ambient temperature range

-25 ... +60 °C

Conformal coating

Coating of the printed circuit boards and the electronic components

Technical data

The technical data of the standard product applies except for the ambient conditions.

Compliant with the standards for electronic equipment used on railway rolling stock (EN 50155, temperature T1, category 1).

No

Ambient conditions

 

Relative humidity

5 … 100 %

Condensation permissible


For further technical documentation on SIPLUS, see:
http://www.siemens.com/siplus-extreme

The CPU 315F-2 DP permits the design of a fail-safe automation system for plants with increased safety requirements, especially for production engineering.

Distributed I/O stations containing fail-safe I/O modules can be connected through the integrated PROFIBUS DP interface. The fail-safe I/O modules of ET 200M can also be centrally implemented safety-related.

Safety-related communication between the F CPU and the fail-safe I/O modules is performed on the basis of the PROFIsafe profile.

The CPU 315F-2 DP features the following:

  • Microprocessor;
    the processor achieves a processing time of approximately 50 ns per binary instruction and 0.45 µs per floating-point operation.
  • Memory:
    384 KB high-speed RAM for safety-relevant and standard program sections; increased memory space requirements must be expected (5 times larger) if safety-relevant program sections are implemented. 128 KB data memory of the 384 KB work memory can be used for standard applications. SIMATIC Micro Memory Cards (max. 8 MB) as load memories for programs additionally permit storage of the project (including symbols and comments) in the CPU.
  • Flexible expansion capability;
    max. 32 modules, (4-tier configuration)
  • MPI multi-point interface;
    the integrated MPI interface can establish as many as 16 connections simultaneously to S7-300/400 or to programming device, PC, OP. Of these connections, one is always reserved for programming devices and another for OPs. The MPI makes it possible to set up a simple network with a maximum of 16 CPUs via "global data communication".
  • PROFIBUS DP interface:
    The CPU 315F-2 DP with PROFIBUS DP master/slave interface allows a distributed automation configuration offering high speed and ease of use. From the user's point of view, the distributed I/O is handled in the same manner as central I/O (identical configuration, addressing and programming).
    Distributed I/O stations with fail-safe I/O modules can be connected via the integral PROFIBUS DP interface. The fail-safe I/O modules of ET 200M can also be installed in central, safety-related configurations.
    The safety-oriented communication between the F-CPU and the fail-safe I/O modules is performed on the basis of the PROFIsafe profile.
  • Password protection;
    a password concept protects the user program from unauthorized access.
  • Diagnostics buffer;
    the last 500 errors and interrupt events are saved in a buffer for diagnostic purposes.
  • Maintenance-free data back-up;
    all standard data is automatically written onto the SIMATIC Micro Memory Card by the CPU if there is a voltage interruption, and is available unchanged following voltage recovery.

Parameterizable properties

The S7 configuration as well as the properties and response of the CPUs can be parameterized using STEP 7:

  • MPI multi-point interface;
    determining station addresses
  • Restart/cycle time behavior;
    stipulation of maximum cycle time and loading as well as self-test functions
  • Clock memory;
    setting of addresses
  • Protection level;
    specifying the access rights to program and data
  • System diagnostics;
    determining handling and scope of the diagnostic alarms
  • Watchdog interrupts;
    setting of periodicity
  • Clock interrupts;
    setting of start date, start time and periodicity
  • PROFIBUS DP master/slave interface;
    user-defined address assignment for distributed I/O

Display and information functions

  • Status and error indications;
    LEDs indicate hardware, programming, time or I/O errors, and operating statuses such as RUN, STOP and start-up.
  • Test functions;
    the PG is used to indicate signal status during program execution, to modify process variables independently of the user program and to output the contents of stack memories.
  • Information functions;
    you can use the PG to obtain information about the storage capacity and operating mode of the CPU , the current utilization of the main and load memories as well as current cycle times and diagnostic buffer contents in plain text.

Integrated communication functions

  • PG/OP communication
  • Global data communication
  • S7 basic communication
  • S7 communication (server only)
  • Routing
  • Data block routing

Communication

The safety-related and standard communication between the central controller and the distributed stations is performed via PROFIBUS DP. The specially developed PROFIBUS profile PROFIsafe allows user data for the safety function to be transferred within the standard data message frame. Additional hardware components, such as special safety buses, are not necessary. The necessary software is either integrated in the hardware components as an expansion of the operating system or it is loaded into the CPU as a certified software block.

System functions

The CPU provides many extensive system functions for diagnostics, parameterization, synchronization, alerting, time measurement, etc.
For further details, see the manual.

Mode of operation

The safety functions of the F-CPU are included in the F program of the CPU and in the fail-safe signal modules.

The signal modules monitor the input and output signals through discrepancy analyses and the application of test signals.

The CPU checks that the controller is operating correctly by means of periodic self-tests, test instructions as well as logical and time-based program execution checks. The I/O is checked with requests for a sign of life.

If an error is diagnosed in the system, it is transferred to a safe state.

An F runtime license is not required for operating the S7-300F-2 DP.

Programming

The S7-300F is programmed in the same manner as the other SIMATIC S7 systems. The user program for non fail-safe system components is created using the familiar programming tools, e.g. STEP 7.

SIMATIC S7 Distributed Safety option package

The STEP 7 option package "SIMATIC S7 Distributed Safety" is required for programming the safety-related program sections. The package contains all the functions and blocks required to create the F program.

The F program with the safety functions is created in F-FBD or F-LAD or using special function blocks from the F library. Use of F-FBD or F-LAD simplifies configuration and programming of the plant and, due to the cross-plant, uniform presentation, also acceptance testing. The programmer can therefore concentrate entirely on configuring the safety-related application, without the need to use any additional tools.

 

6ES7 315-6FF04-0AB0

Product version

 

Hardware product version

01

Firmware version

V3.3

General information

 

associated programming package

STEP 7 V5.5 + SP1 or higher or STEP7 V5.2 + SP1 or higher with HSP 218 + Distributed Safety

Supply voltage

 

24 V DC

Yes

Input current

 

Current consumption (rated value)

850 mA

Current consumption (in no-load operation), typ.

150 mA

Inrush current, typ.

3.5 A

I²t

1 A²·s

Power losses

 

Power loss, typ.

4.5 W

Memory

 

Work memory

 

  • integrated

384 Kibyte

  • expandable

No

  • Size of retentive memory for retentive data blocks

128 Kibyte

Load memory

 

  • pluggable (MMC)

Yes

  • pluggable (MMC), max.

8 Mbyte

  • Data management on MMC (after last programming), min.

10 a

Backup

 

  • present

Yes; Guaranteed by MMC (maintenance-free)

  • without battery

Yes; Program and data

CPU-blocks

 

Number of blocks (total)

1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

DB

 

  • Number, max.

1 024; Number range: 1 to 16000

  • Size, max.

64 Kibyte

FB

 

  • Number, max.

1 024; Number range: 0 to 7999

  • Size, max.

64 Kibyte

FC

 

  • Number, max.

1 024; Number range: 0 to 7999

  • Size, max.

64 Kibyte

OB

 

  • Size, max.

64 Kibyte

Nesting depth

 

  • per priority class

16

  • additional within an error OB

4

CPU processing times

 

for bit operations, min.

0.05 µs

for word operations, min.

0.09 µs

for fixed point arithmetic, min.

0.12 µs

for floating point arithmetic, min.

0.45 µs

Counters, timers and their retentivity

 

S7 counter

 

  • Number

256

  • Retentivity

 

    • adjustable

Yes

    • lower limit

0

    • upper limit

255

    • preset

Z 0 to Z 7

  • Counting range

 

    • lower limit

0

    • upper limit

999

IEC counter

 

  • present

Yes

  • Type

SFB

  • Number

Unlimited (limited only by RAM capacity)

S7 times

 

  • Number

256

  • Retentivity

 

    • adjustable

Yes

    • lower limit

0

    • upper limit

255

    • preset

No retentivity

  • Time range

 

    • lower limit

10 ms

    • upper limit

9 990 s

IEC timer

 

  • present

Yes

  • Type

SFB

  • Number

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

 

retentive data area, total

All, 128 KB max.

Flag

 

  • Number, max.

2 048 byte

  • Retentivity available

Yes; MB 0 to MB 2047

  • Retentivity preset

MB 0 to MB 15

  • Number of clock memories

8; 1 memory byte

Data blocks

 

  • Retentivity adjustable

Yes; via non-retain property on DB

  • Retentivity preset

Yes

Local data

 

  • per priority class, max.

32 Kibyte; Max. 2 KB per block

Address area

 

I/O address area

 

  • Inputs

2 048 byte

  • Outputs

2 048 byte

  • of which, distributed

 

    • Inputs

2 048 byte

    • Outputs

2 048 byte

Process image

 

  • Inputs, adjustable

2 048 byte

  • Outputs, adjustable

2 048 byte

  • Inputs, default

384 byte

  • Outputs, default

384 byte

Subprocess images

 

  • Number of subprocess images, max.

1

Digital channels

 

  • Inputs

16 384

  • Outputs

16 384

  • Inputs, of which central

1 024

  • Outputs, of which central

1 024

Analog channels

 

  • Inputs

1 024

  • Outputs

1 024

  • Inputs, of which central

256

  • Outputs, of which central

256

Hardware configuration

 

Racks, max.

4

Modules per rack, max.

8

Expansion devices, max.

3

Number of DP masters

 

  • integrated

1

  • via CP

4

Number of operable FMs and CPs (recommended)

 

  • FM

8

  • CP, point-to-point

8

  • CP, LAN

10

Time of day

 

Clock

 

  • Hardware clock (real-time clock)

Yes

  • battery-backed and synchronizable

Yes

  • Deviation per day, max.

10 s; Typ.: 2 s

  • Backup time

6 wk; At 40 °C ambient temperature

  • Behavior of the clock following POWER-ON

Clock continues running after POWER OFF

  • Behavior of the clock following expiry of backup period

Clock continues to run with the time at which the power failure occurred

Operating hours counter

 

  • Number

1

  • Number/Number range

0

  • Range of values

0 to 2^31 hours (when using SFC 101)

  • Granularity

1 hour

  • retentive

Yes; Must be restarted at each restart

Clock synchronization

 

  • supported

Yes

  • to MPI, master

Yes

  • to MPI, slave

Yes

  • to DP, master

Yes; With DP slave only slave clock

  • to DP, slave

Yes

  • in AS, master

Yes

  • in AS, slave

No

1st interface

 

Type of interface

Integrated RS 485 interface

Physics

RS 485

Isolated

No

Power supply to interface (15 to 30 V DC), max.

200 mA

Functionality

 

  • MPI

Yes

  • DP master

No

  • DP slave

No

  • Point-to-point connection

No

MPI

 

  • Services

 

    • PG/OP communication

Yes

    • Routing

Yes

    • Global data communication

Yes

    • S7 basic communication

Yes

    • S7 communication

Yes; Only server, configured on one side

    • S7 communication, as client

No

    • S7 communication, as server

Yes

  • Transmission rate, max.

187.5 kbit/s

2nd interface

 

Type of interface

Integrated RS 485 interface

Physics

RS 485

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

200 mA

Functionality

 

  • MPI

No

  • DP master

Yes

  • DP slave

Yes

  • Local Operating Network

No

DP master

 

  • Services

 

    • PG/OP communication

Yes

    • Global data communication

No

    • S7 basic communication

Yes; I blocks only

    • S7 communication

Yes; Only server, configured on one side

    • S7 communication, as client

No

    • S7 communication, as server

Yes

    • Equidistance mode support

Yes

    • Isochronous mode

Yes; OB 61

    • SYNC/FREEZE

Yes

    • Activation/deactivation of DP slaves

Yes

    • Number of DP slaves that can be simultaneously activated/deactivated, max.

8

    • DPV1

Yes

  • Transmission rate, max.

12 Mbit/s

  • Number of DP slaves, max.

124; Per station

  • Address area

 

    • Inputs, max.

2 048 byte

    • Outputs, max.

2 048 byte

  • User data per DP slave

 

    • Inputs, max.

244 byte

    • Outputs, max.

244 byte

DP slave

 

  • Services

 

    • PG/OP communication

Yes

    • Global data communication

No

    • S7 basic communication

No

    • S7 communication

Yes; Only server, configured on one side

    • S7 communication, as client

No

    • S7 communication, as server

Yes

    • Direct data exchange (slave-to-slave communication)

Yes

    • DPV1

No

  • GSD file

The latest GSD file is available at: http://www.siemens.de/profibus-gsd

  • Transmission rate, max.

12 Mbit/s

  • Automatic baud rate search

Yes; only with passive interface

  • Transfer memory

 

    • Inputs

244 byte

    • Outputs

244 byte

  • Address area, max.

32

  • User data per address area, max.

32 byte

Communication functions

 

PG/OP communication

Yes

Data record routing

Yes

Global data communication

 

  • supported

Yes

  • Number of GD loops, max.

8

  • Number of GD packets, max.

8

  • Number of GD packets, transmitter, max.

8

  • Number of GD packets, receiver, max.

8

  • Size of GD packets, max.

22 byte

  • Size of GD packet (of which consistent), max.

22 byte

S7 basic communication

 

  • supported

Yes

  • User data per job, max.

76 byte

  • User data per job (of which consistent), max.

76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

S7 communication

 

  • supported

Yes

  • as server

Yes

  • as client

Yes; Via CP and loadable FB

  • User data per job, max.

180 byte; With PUT/GET

  • User data per job (of which consistent), max.

240 byte; as server

S5-compatible communication

 

  • supported

Yes; via CP and loadable FC

S7 message functions

 

Number of login stations for message functions, max.

16; Depending on the configured connections for PG/OP and S7 basic communication

Process diagnostic messages

Yes

simultaneously active Alarm-S blocks, max.

300

Test commissioning functions

 

Status/control

 

  • Status/control variable

Yes

  • Variables

Inputs, outputs, memory bits, DB, times, counters

  • Number of variables, max.

30

  • of which status variables, max.

30

  • of which control variables, max.

14

Forcing

 

  • Forcing

Yes

  • Force, variables

Inputs, outputs

  • Number of variables, max.

10

Status block

Yes; Up to 2 simultaneously

Single step

Yes

Number of breakpoints

4

Diagnostic buffer

 

  • present

Yes

  • Number of entries, max.

500

    • adjustable

No

    • Of which powerfail-proof

100; Only the last 100 entries are retained

  • Number of entries readable in RUN, max.

 

    • adjustable

Yes; From 10 to 499

    • preset

10

Isochronous mode

 

Isochronous mode

Yes

Ambient conditions

 

Operating temperature

 

  • Min.

0 °C

  • max.

60 °C

Configuration

 

programming

 

  • Programming language

 

    • LAD

Yes

    • FBD

Yes

    • STL

Yes

    • SCL

Yes

    • CFC

Yes

    • GRAPH

Yes

    • HiGraph®

Yes

  • Command set

see instruction list

  • Nesting levels

8

Know-how protection

 

  • User program protection/password protection

Yes

  • Block encryption

Yes; With S7 block Privacy

Dimensions

 

Width

40 mm

Height

125 mm

Depth

130 mm

Weight

 

Weight, approx.

290 g


Код Заказной номер Описание Вес (кг) Заказать
60610 6AG1315-6FF04-2AB0 siplus s7-300, cpu 315f-2dp, расширенный диапазон рабочих температур -25... +60 град. цельсия, с конформным покрытием, на основе 6es7315-6ff04-0ab0. failsafe-cpu с интерфейсом mpi, встроенным источником питания =24 в, 384 кбайт рабочей памяти 2.интерфейс 0.363 Заказать
110756 6ES7391-1AA00-0AA0 simatic s7-300, запасной съемный соединитель для подключения цепей питания =24в к центральным процессорам s7-300 compact и модулю fm352-5, упаковка из 10 штук 0.061 Заказать
110780 6ES7398-8EA00-8AA0 simatic s7-300/-400, руководство по связи s7-300/-400, немецкий язык 0.585 Заказать
110781 6ES7398-8EA00-8BA0 simatic s7-300/-400, руководство по связи s7-300/-400, английский язык 0.568 Заказать
110782 6ES7398-8FA10-8AA0 simatic s7-300 compact, руководство по конфигурированию, технические характеристики центральных процессоров, технические характеристики модулей, список инструкций, немецкий язык 5 Заказать
110783 6ES7398-8FA10-8BA0 simatic s7-300 compact, руководство по конфигурированию, технические характеристики центральных процессоров, технические характеристики модулей, список инструкций, английский язык 5 Заказать
63144 6ES7833-1FC02-0YA5 simatic s7, f средство разработки распределенных систем повышенной безопасности distributed safety v5.4, плавающая лицензия для 1 пользователя, инженерное прогр. обеспечение, прогр. обесп. и документация на cd, class a, 3 языка (нем., англ.,франц.), работа под step7 v5.3 sp3 0.257 Заказать
63145 6ES7833-1FC02-0YE5 simatic s7, f средство программирования distributed safety v5.4, пакет обновления от версии 5.x до версии 5.4, плавающая лицензия для 1 пользователя, инженерное прогр. обеспечение, прогр. обесп. и документация на cd, class a, 3 языка (нем., англ.,франц.), работа под step7 v5.3 sp3 0.257 Заказать
63182 6ES7901-0BF00-0AA0 simatic s7, mpi-кабель для подключения simatic s7 к программатору через mpi, длина 5m 0.274 Заказать
111168 6ES7912-0AA00-0AA0 simatic s7, пластиковые метки маркироки номеров модулей в монтажных стойках s7-300/ s7-400/ et 200m/ c7 0.006 Заказать
111241 6ES7953-8LF20-0AA0 simatic s7, микрокарта памяти mmc для s7-300/c7/et 200, 3.3 в nflash, 64 кбайт 0.012 Заказать
111242 6ES7953-8LG20-0AA0 simatic s7, микрокарта памяти mmc для s7-300/c7/et 200, 3.3 в nflash, 128 кбайт 0.014 Заказать
111243 6ES7953-8LJ30-0AA0 simatic s7, micro memory card f. s7-300/c7/et 200, 3.3 v nflash, 512 kbytes 0.012 Заказать
111244 6ES7953-8LL20-0AA0 simatic s7, микрокарта памяти mmc для s7-300/c7/et 200, 3.3 в nflash, 2 мбайт 0.012 Заказать
111245 6ES7953-8LM20-0AA0 simatic s7, микрокарта памяти mmc для s7-300/c7/et 200, 3.3 в nflash, 4 мбайт 0.012 Заказать
111246 6ES7953-8LP20-0AA0 simatic s7, микрокарта памяти mmc для s7-300/c7/et 200, 3.3 в nflash, 8 мбайт 0.013 Заказать
111255 6ES7972-0AA02-0XA0 simatic dp, rs485-повторитель для подключения шинной системы profibus/mpi bus systems с макс. 31 узлом; макс. 12 мбит/с, степень защиты ip20, улучшенные пользовательские свойства 0.289 Заказать
63269 6ES7972-0BA12-0XA0 simatic dp, соединитель для подключения к profibus, до 12 мбит/с, отвод кабеля под углом 90 градусов, 15.8 x 54 x 34 mm, с встроенным терминальным резистором, с функциями разделения, без гнезда для подключения программатора 0.049 Заказать
111257 6ES7972-0BA52-0XA0 simatic dp, шинный оединитель для подключения к сетям profibus до 12 мбит/с, отвод кабеля под углом 90 градусов, 15,8 x 59 x 35,6 mm (шxвxг), ipcd, технология fast connect, без разъёма для подключения программатора 0.044 Заказать
111258 6ES7972-0BA52-0XB0 simatic dp,bus connector for profibus up to 12 mbit/s 90 degree angle outgoing cable, 15,8 x 59 x 35,6 mm (wxhxd), ipcd techology fast connect, without pg socket 100 pieces per packaging unit 4.5 Заказать
111260 6ES7972-0BB12-0XA0 simatic dp, соединитель для подключения к profibus, до 12 мбит/с, отвод кабеля под углом 90 градусов, 15.8 x 54 x 34 mm, с встроенным терминальным резистором, с функциями разделения, с гнездом для подключения программатора 0.056 Заказать
63271 6ES7972-0BB52-0XA0 simatic dp, шинный оединитель для подключения к сетям profibus до 12 мбит/с, отвод кабеля под углом 90 градусов, 15,8 x 59 x 35,6 mm (шxвxг), ipcd, технология fast connect, с разъёмом для подключения программатора 0.049 Заказать
111262 6ES7972-0BB52-0XB0 simatic dp,bus connector for profibus up to 12 mbit/s 90 degree angle outgoing cable, 15,8 x 59 x 35,6 mm (wxhxd), ipcd techology fast connect, with pg socket 100 pieces per packaging unit 5 Заказать
63274 6ES7972-0CB20-0XA0 simatic s7, pc usb адаптер для подкл. simatic s7-200/s7-300/ s7-400/ c7 к компьютеру/ программатору через usb интерфейс: pc usb адаптер, cd с набором драйверов и док., usb кабель длиной 5 м, mpi кабель длиной 0.3 м. работа под упр. win 2000/xp 0.526 Заказать
63287 6ES7998-8XC01-8YE0 коллекция руководств simatic на cd-rom. pdf-формат, анг/ нем/ фр/ исп/ ит. язык. все руководства по s7-200/ -300/ -400/ -c7/ -logo!; simatic dp/ -pc/ -pg; step7, инстр. средствам проектирования, прогр. обеспечению runtime, simatic pcs7/ hmi/ net 0.2 Заказать
63288 6ES7998-8XC01-8YE2 коллекция руководств simatic на cd-rom, 5-языковая поддержка (без русского), служба обновления в течение 1 года 0.4 Заказать
114346 6GK1500-0EA02 simatic net, pb шинный соединитель с осевым отводом кабеля для пром. пк, simatic op, olm; скорость передачи 12 мбит/с, оконечный резистор с функциями разделения 0.104 Заказать