SIPLUS CPU 417H производства Siemens

SIPLUS CPU 417H

CPU for SIMATIC S7-400H and S7-400F/FH

  • Usable in high-availability systems such as the S7-400H
  • Usable with F runtime license as F-capable CPU in S7-400F/FH safety-related systems
  • With integral PROFIBUS DP master interface
  • Features 2 slots for sync modules

Note:

SIPLUS extreme products are based on Siemens Industry standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.

 

SIPLUS CPU 417H

Order number

6AG1 417-4HT14-4AB0

Order No. based on

6ES7 417-4HT14-0AB0

Ambient temperature range

0 ... +60 °C

Conformal coating

Coating of the printed circuit boards and the electronic components

Technical data

The technical data of the standard product applies except for the environmental conditions

Ambient conditions

Relative humidity

5 ... 100 %
Condensation permissible

Biologically active substances

Conformity with EN 60721‑3‑3, Class 3B2 mold and fungal spores (except fauna)

Chemically active substances

Conformity with EN 60721‑3‑3, Class 3C4 incl. salt mist and ISA–S71.04 severity level G1; G2; G3; GX 1)2)

Mechanically active substances

Conformity with EN 60721‑3‑3, Class 3S4 including conductive sand, dust 2)

Air pressure (depending on the highest positive temperature range specified)

1080 ... 795 hPa (-1000 ... +2000 m)
see ambient temperature range

795 ... 658 hPa (+2000 ... +3500 m)
derating 10 K

658 ... 540 hPa (+3500 ... +5000 m)
derating 20 K


1) ISA-S71.04 severity level GX: Long-term load: SO2 < 4.8 ppm; H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm; HF < 0.12 ppm; NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm
Limit value (max. 30 min/d): SO2 < 17.8 ppm; H2S < 49.7 ppm; Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm; NH < 247 ppm; O3 < 1.0 ppm; NOX < 10.4 ppm

2) The supplied plug covers must remain in place over the unused interface when operated in atmospheres containing corrosive gases!

The technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme

The CPU 417-4H is the most powerful CPU for the SIMATIC S7-400H and S7-400F/FH. It allows a fault-tolerant S7-400H system to be configured. It can also be used for the failsafe S7-400F/FH automation system in conjunction with an F-runtime license.

The integrated PROFIBUS DP interface supports direct connection to the PROFIBUS DP fieldbus as master.

The CPU 417-4H features:

  • A powerful processor:
    The CPU achieves command runtimes as little as 18 ns per binary command.
  • 30 MB main memory (15 MB for programs, 15 MB for data):
    Load memory for user programs and configuration data for the S7-400H automation system; Fast main memory for subroutines of the user program that are relevant to the process.
  • A memory card:
    For expanding the integrated load memory. In addition to the program itself, the information contained in the load memory also includes configuration data for the S7-400H, which is why it takes up twice as much space in the memory. The result is that:
    • The integrated load memory is not sufficient for large programs, which is why the memory card is often required.
      RAM and FEPROM cards are available (FEPROM for saving at zero voltage too).
  • Easy expandability:
    Max. 128K digital and 8K analog inputs/outputs.
  • Multipoint-capable MPI interface:
    The MPI enables the creation of a simple network with max. 32 nodes and a data transfer rate of 187.5 Kbit/s. The CPU can establish up to 64 connections to users of the communication bus (C bus) and the MPI.
    Note:
    If PROFIBUS DP and MPI interfaces are being used simultaneously, only the following bus connectors can be connected to the MPI interface:
    • With socket: 6ES7 972-0BB41-0XA0
    • Without socket: 6ES7 972-0BA41-0XA0
  • Mode selector:
    Designed as a toggle switch.
  • Diagnostics buffer:
    The last 120 alarm and interrupt events are stored in a ring buffer for the purpose of diagnosis.
  • Real-time clock:
    Diagnostics reports from the CPU are provided with the date and time.
  • PROFIBUS DP interface:
    The CPU 417-4H with PROFIBUS DP master interface enables distributed automation to be established at high speed and with easy operation. From the user's point of view, the distributed I/Os are treated like centralized I/Os (same configuration, addressing and programming).
    Note:
    If PROFIBUS DP and MPI interfaces are being used simultaneously, only the following bus connectors can be connected to the MPI interface:
    • With socket: 6ES7 972-0BB41-0XA0
    • Without socket: 6ES7 972-0BA41-0XA0
  • Block protection:
    A password concept also protects the user program from unauthorized access as well as the keyswitch.
  • Integrated HMI services:
    The user only has to specify the source and destination of the data with HMI devices. The data are then transported cyclically and automatically by the system.
  • Integrated communication functions:
    • PG/OP communication
    • Expanded communication (simple and high-availability)
Configurable Attributes

The STEP 7 "hardware configuration" tool and the installed S7-400H options package are used to configure the features and response of the S7-400H, including the CPUs, for example:

  • Multipoint interface MPI:
    • Definition of node addresses
    • Startup/cycle behavior
    • Stipulation of the maximum cycle time and communication load
  • Address allocation:
    Addressing of I/O modules
  • Retentive area:
    Definition of the number of retentive bit memories, counters, timers, data blocks, and clock memories
  • Protection level:
    Definition of access authorizations to program and data
  • System diagnostics:
    Definition of the handling and scope of diagnostics messages
  • Timed interrupts:
    Setting of periods
  • Configuration of H stations
Safety-related functions

The F-runtime license can be used to compile the failsafe F user program and run it on the CPU. A license is required for each S7-400F/FH system. 2 TÜV stickers are included.

Reporting functions
  • Status and fault indicators:
    LEDs indicate internal and external errors and operating modes such as RUN, STOP, Startup, "Master” mode, redundancy error, test function, etc.
  • Test functions:
    The PG can be used to display signal states in program execution, modify process tags irrespective of the user program, read out the contents of stack memories, run separate program steps and inhibit program components.
  • Information functions:
    The PG can be used to provide the user with information about the memory capacity and operating mode of the CPU, and the current utilization of the working and load memories.

 

6ES7 417-4HT14-0AB0

Product version

 

Hardware product version

1

Firmware version

V4.5

General information

 

associated programming package

STEP7 V 5.3 SP2 or higher with HW update

CiR - Configuration in RUN

 

CiR synchronization time, basic load

60 ms

CiR synchronization time, time per I/O slave

10 µs

Supply voltage

 

24 V DC

No; Power supply via system power supply

Input current

 

from backplane bus 5 V DC, max.

1.8 A

from interface 5 V DC, max.

90 mA; At each DP interface

Power losses

 

Power loss, typ.

6.5 W

Memory

 

Work memory

 

  • integrated

30 Mbyte

  • integrated (for program)

15 Mbyte

  • integrated (for data)

15 Mbyte

  • expandable

No

Load memory

 

  • expandable FEPROM

Yes

  • expandable FEPROM, max.

64 Mbyte

  • integrated RAM, max.

256 Kibyte

  • expandable RAM

Yes

  • expandable RAM, max.

64 Mbyte

Backup

 

  • present

Yes

  • with battery

Yes; all data

  • without battery

No

CPU-blocks

 

DB

 

  • Number, max.

8 191; Number range: 1 - 8191

  • Size, max.

64 Kibyte

FB

 

  • Number, max.

6 144; Number range: 0 - 6143

  • Size, max.

64 Kibyte

FC

 

  • Number, max.

6 144; Number range: 0 - 6143

  • Size, max.

64 Kibyte

OB

 

  • Size, max.

64 Kibyte

Nesting depth

 

  • per priority class

24

  • additional within an error OB

2

CPU processing times

 

for bit operations, min.

0.018 µs

for word operations, min.

0.018 µs

for fixed point arithmetic, min.

0.018 µs

for floating point arithmetic, min.

0.054 µs

Counters, timers and their retentivity

 

S7 counter

 

  • Number

2 048

  • Retentivity

 

    • adjustable

Yes

    • lower limit

0

    • upper limit

2 047

    • preset

Z 0 to Z 7

  • Counting range

 

    • lower limit

0

    • upper limit

999

IEC counter

 

  • present

Yes

  • Type

SFB

S7 times

 

  • Number

2 048

  • Retentivity

 

    • adjustable

Yes

    • lower limit

0

    • upper limit

2 047

    • preset

No times retentive

  • Time range

 

    • lower limit

10 ms

    • upper limit

9 990 s

IEC timer

 

  • present

Yes

  • Type

SFB

Data areas and their retentivity

 

retentive data area, total

Total working and load memory (with backup battery)

Flag

 

  • Number, max.

16 Kibyte

  • Retentivity available

Yes

  • Retentivity preset

MB 0 to MB 15

  • Number of clock memories

8; (in 1 memory byte)

Local data

 

  • adjustable, max.

64 Kibyte

  • preset

32 Kibyte

Address area

 

I/O address area

 

  • Inputs

16 Kibyte

  • Outputs

16 Kibyte

  • of which, distributed

 

    • MPI/DP interface, inputs

2 Kibyte

    • MPI/DP interface, outputs

2 Kibyte

    • DP interface, inputs

8 Kibyte

    • DP interface, outputs

8 Kibyte

Process image

 

  • Inputs, adjustable

16 Kibyte

  • Outputs, adjustable

16 Kibyte

  • Inputs, default

1 024 byte

  • Outputs, default

1 024 byte

  • consistent data, max.

244 byte

  • Access to consistent data in process image

Yes

Subprocess images

 

  • Number of subprocess images, max.

15

Digital channels

 

  • Inputs

131 072

  • Outputs

131 072

  • Inputs, of which central

131 072

  • Outputs, of which central

131 072

Analog channels

 

  • Inputs

8 192

  • Outputs

8 192

  • Inputs, of which central

8 192

  • Outputs, of which central

8 192

Hardware configuration

 

Expansion devices, max.

21

Multicomputing

No

Interface modules

 

  • Number of connectable IMs (total), max.

6

  • Number of connectable IM 460s, max.

6

  • Number of connectable IM 463s, max.

4; Single mode only

Number of DP masters

 

  • integrated

2

  • via CP

10

  • Mixed mode IM + CP permitted

No

Number of operable FMs and CPs (recommended)

 

  • FM

See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections

  • CP, point-to-point

See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections

  • PROFIBUS and Ethernet CPs

14; Of which max. 10 CP as DP master

Time of day

 

Clock

 

  • Hardware clock (real-time clock)

Yes

  • battery-backed and synchronizable

Yes

  • Resolution

1 ms

  • Deviation per day (buffered), max.

1.7 ms; Power off

  • Deviation per day (unbuffered) max.

8.6 ms; Power on

Operating hours counter

 

  • Number

8

  • Number/Number range

0 to 7

  • Range of values

0 to 32767 hours

  • Granularity

1 hour

  • retentive

Yes

Clock synchronization

 

  • supported

Yes

  • to MPI, master

Yes

  • to MPI, slave

Yes

  • to DP, master

Yes

  • to DP, slave

Yes

  • in AS, master

Yes

  • in AS, slave

Yes

1st interface

 

Type of interface

integrated

Physics

RS 485 / PROFIBUS + MPI

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

150 mA

Number of connection resources

MPI: 44, DP: 32

Functionality

 

  • MPI

Yes

  • DP master

Yes

  • DP slave

No

MPI

 

  • Number of connections

44

  • Services

 

    • PG/OP communication

Yes

    • Routing

Yes

    • Global data communication

No

    • S7 basic communication

No

    • S7 communication

Yes

    • S7 communication, as client

Yes

    • S7 communication, as server

Yes

  • Transmission rate, max.

12 Mbit/s

DP master

 

  • Number of connections, max.

32

  • Services

 

    • PG/OP communication

Yes

    • Global data communication

No

    • S7 basic communication

No

    • S7 communication

Yes

    • S7 communication, as client

Yes

    • S7 communication, as server

Yes

    • Equidistance mode support

No

    • SYNC/FREEZE

No

    • Activation/deactivation of DP slaves

No

    • Direct data exchange (slave-to-slave communication)

No

  • Transmission rate, max.

12 Mbit/s

  • Number of DP slaves, max.

32

  • Address area

 

    • Inputs, max.

2 Kibyte

    • Outputs, max.

2 Kibyte

  • User data per DP slave

 

    • User data per DP slave, max.

244 byte

    • Inputs, max.

244 byte

    • Outputs, max.

244 byte

    • Slots, max.

244

    • per slot, max.

128 byte

2nd interface

 

Type of interface

integrated

Physics

RS 485 / PROFIBUS + MPI

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

150 mA

Number of connection resources

32

Functionality

 

  • DP master

Yes

  • DP slave

No

DP master

 

  • Number of connections, max.

32

  • Services

 

    • PG/OP communication

Yes

    • Global data communication

No

    • S7 basic communication

No

    • S7 communication

Yes

    • Equidistance mode support

No

    • SYNC/FREEZE

No

    • Direct data exchange (slave-to-slave communication)

No

  • Transmission rate, max.

12 Mbit/s

  • Number of DP slaves, max.

125

  • Address area

 

    • Inputs, max.

8 Kibyte

    • Outputs, max.

8 Kibyte

  • User data per DP slave

 

    • User data per DP slave, max.

244 byte

    • Inputs, max.

244 byte

    • Outputs, max.

244 byte

    • Slots, max.

244

    • per slot, max.

128 byte

3rd interface

 

Type of interface

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization submodule IF 960 6ES7 960-1AA04-0XA0 or 6ES7 960-1AB04-0XA0

4th interface

 

Type of interface

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization submodule IF 960 6ES7 960-1AA04-0XA0 or 6ES7 960-1AB04-0XA0

Communication functions

 

PG/OP communication

Yes

  • Number of connectable OPs without message processing

63

  • Number of connectable OPs with message processing

16

Global data communication

 

  • supported

No

S7 basic communication

 

  • supported

No

S7 communication

 

  • supported

Yes

  • as server

Yes

  • as client

Yes

  • User data per job, max.

64 Kibyte

  • User data per job (of which consistent), max.

462 byte; 1 variable

S5-compatible communication

 

  • supported

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

  • User data per job, max.

8 Kibyte

  • User data per job (of which consistent), max.

240 byte

  • Number of simultaneous AG-SEND/AG-RECV orders per CPU, max.

64/64

Standard communication (FMS)

 

  • supported

Yes; Via CP and loadable FB

Number of connections

 

  • overall

64

S7 message functions

 

Number of login stations for message functions, max.

16

Symbol-related messages

No

Block related messages

Yes

simultaneously active Alarm-S blocks, max.

200

Alarm 8-blocks

Yes

  • Number of instances for alarm 8 and S7 communication blocks, max.

10 000

  • preset, max.

1 200

Process control messages

Yes

Test commissioning functions

 

Status/control

 

  • Status/control variable

Yes

  • Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

  • Number of variables, max.

70

Forcing

 

  • Forcing

Yes

  • Force, variables

Inputs/outputs, bit memories, distributed I/Os

  • Number of variables, max.

512

Status block

Yes

Single step

Yes

Number of breakpoints

4

Diagnostic buffer

 

  • present

Yes

  • Number of entries, max.

3 200

    • adjustable

Yes

    • preset

120

Configuration

 

Configuration software

 

  • STEP 7

Yes; With hardware update as of STEP7 V5.3 SP2

programming

 

  • Programming language

 

    • LAD

Yes

    • FBD

Yes

    • STL

Yes

    • SCL

Yes

    • CFC

Yes

    • GRAPH

Yes

    • HiGraph®

Yes

  • Command set

see instruction list

  • Nesting levels

8

Know-how protection

 

  • User program protection/password protection

Yes

Dimensions

 

Width

50 mm

Height

290 mm

Depth

219 mm

Required slots

2

Weight

 

Weight, approx.

995 g


Код Заказной номер Описание Вес (кг) Заказать
109122 6AG1417-4HT14-4AB0 siplus s7-400 cpu417h для тяжёлых условий применения на основе 6es7417-4ht14-0ab0 0.3 Заказать
110780 6ES7398-8EA00-8AA0 simatic s7-300/-400, руководство по связи s7-300/-400, немецкий язык 0.585 Заказать
110781 6ES7398-8EA00-8BA0 simatic s7-300/-400, руководство по связи s7-300/-400, английский язык 0.568 Заказать
63141 6ES7833-1CC00-6YX0 simatic s7-400f/fh, f-runtime лицензия на выполнение f-программ.кв устанавливается на каждый центральный процессор cpu 414h/ cpu 416h, используемый в системах simatc s7-400f/fh 0.047 Заказать
111123 6ES7833-1CC02-0YA5 simatic s7, f-prog-sw u.fb-lib. float. license f.1 installation r-sw, sw and docu. on cd, class a, 2 languages (g,e), executable under winxp sp2/sp3, win server 2003 sp2 reference-hw:simatic s7-400h reference-hw:simatic s7-400h 0.245 Заказать
111124 6ES7833-1CC02-0YE5 simatic s7, f-prog-sw a.fb-lib. upgrade v5.x/6.0 single license to v6.1 floating license r-sw, sw and docu. on cd, class a, 2 languages (g,e), executable under winxp sp2/sp3, win server 2003 sp2 reference-hw:simatic s7-400h cpu412h/414h/417h 0.245 Заказать
63182 6ES7901-0BF00-0AA0 simatic s7, mpi-кабель для подключения simatic s7 к программатору через mpi, длина 5m 0.274 Заказать
111168 6ES7912-0AA00-0AA0 simatic s7, пластиковые метки маркироки номеров модулей в монтажных стойках s7-300/ s7-400/ et 200m/ c7 0.006 Заказать
63251 6ES7952-1AK00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, ram, 1 мбайт 0.052 Заказать
111236 6ES7952-1AL00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, ram, 2 мбайт 0.051 Заказать
111237 6ES7952-1AM00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, ram, 4 мбайт 0.055 Заказать
63252 6ES7952-1AP00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, ram, 8 мбайт 0.052 Заказать
111238 6ES7952-1AS00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, ram, 16 мбайт 0.051 Заказать
63253 6ES7952-1AY00-0AA0 simatic s7, карта памяти ram для s7-400, длинная версия, 64 мбайт 0.053 Заказать
63254 6ES7952-1KK00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, 5в flash-eprom, 1 мбайт 0.051 Заказать
63255 6ES7952-1KL00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, 5в flash-eprom, 2 мбайт 0.052 Заказать
111239 6ES7952-1KM00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, 5в flash-eprom, 4 мбайт 0.049 Заказать
111240 6ES7952-1KP00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, 5в flash-eprom, 8 мбайт 0.05 Заказать
63256 6ES7952-1KS00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, 5в flash-eprom, 16 мбайт 0.052 Заказать
63257 6ES7952-1KT00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, 5в flash-eprom, 32 мбайт 0.047 Заказать
63258 6ES7952-1KY00-0AA0 simatic s7, карта памяти для s7-400, длинное исполнение, 5в flash-eprom, 64 мбайт 0.052 Заказать
63269 6ES7972-0BA12-0XA0 simatic dp, соединитель для подключения к profibus, до 12 мбит/с, отвод кабеля под углом 90 градусов, 15.8 x 54 x 34 mm, с встроенным терминальным резистором, с функциями разделения, без гнезда для подключения программатора 0.049 Заказать
63270 6ES7972-0BA30-0XA0 simatic dp, соединитель для подключения к profibus, до 1.5 мбит/с, с наклонным отводом кабеля, 15 x 58 x 34 mm, без терминального резистора, без гнезда для подключения программатора 0.045 Заказать
111256 6ES7972-0BA42-0XA0 simatic dp, шинный соединитель для подключения к сети profibus до 12 мбит/с, с наклонным отводом кабеля, 15,8 x 54 x 39,5 mm (шxвxг), оконечное сопротивление с функц. изоляции, без разъёма для подключения pg 0.046 Заказать
111257 6ES7972-0BA52-0XA0 simatic dp, шинный оединитель для подключения к сетям profibus до 12 мбит/с, отвод кабеля под углом 90 градусов, 15,8 x 59 x 35,6 mm (шxвxг), ipcd, технология fast connect, без разъёма для подключения программатора 0.044 Заказать
111258 6ES7972-0BA52-0XB0 simatic dp,bus connector for profibus up to 12 mbit/s 90 degree angle outgoing cable, 15,8 x 59 x 35,6 mm (wxhxd), ipcd techology fast connect, without pg socket 100 pieces per packaging unit 4.5 Заказать
111260 6ES7972-0BB12-0XA0 simatic dp, соединитель для подключения к profibus, до 12 мбит/с, отвод кабеля под углом 90 градусов, 15.8 x 54 x 34 mm, с встроенным терминальным резистором, с функциями разделения, с гнездом для подключения программатора 0.056 Заказать
111261 6ES7972-0BB42-0XA0 simatic dp, шинный соединитель для подключения к сети profibus до 12 мбит/с, с наклонным отводом кабеля, 15,8 x 54 x 39,5 mm (шxвxг), оконечное сопротивление с функц. изоляции, с разъёмом для подключения pg 0.051 Заказать
63271 6ES7972-0BB52-0XA0 simatic dp, шинный оединитель для подключения к сетям profibus до 12 мбит/с, отвод кабеля под углом 90 градусов, 15,8 x 59 x 35,6 mm (шxвxг), ipcd, технология fast connect, с разъёмом для подключения программатора 0.049 Заказать
111262 6ES7972-0BB52-0XB0 simatic dp,bus connector for profibus up to 12 mbit/s 90 degree angle outgoing cable, 15,8 x 59 x 35,6 mm (wxhxd), ipcd techology fast connect, with pg socket 100 pieces per packaging unit 5 Заказать
63287 6ES7998-8XC01-8YE0 коллекция руководств simatic на cd-rom. pdf-формат, анг/ нем/ фр/ исп/ ит. язык. все руководства по s7-200/ -300/ -400/ -c7/ -logo!; simatic dp/ -pc/ -pg; step7, инстр. средствам проектирования, прогр. обеспечению runtime, simatic pcs7/ hmi/ net 0.2 Заказать
63288 6ES7998-8XC01-8YE2 коллекция руководств simatic на cd-rom, 5-языковая поддержка (без русского), служба обновления в течение 1 года 0.4 Заказать
114346 6GK1500-0EA02 simatic net, pb шинный соединитель с осевым отводом кабеля для пром. пк, simatic op, olm; скорость передачи 12 мбит/с, оконечный резистор с функциями разделения 0.104 Заказать
116945 6XV1830-0EH10 simatic net, стандартный экранированный profibus кабель для быстрого монтажа (fc), 2-жильный, поставка по метражу отрезками длиной 20 ... 1000 m 0.081 Заказать
;