SITRANS P200 производства Siemens

SITRANS P200

The SITRANS P200 pressure transmitter measures the gauge and absolute pressure of liquids, gases and vapors.

  • Ceramic measuring cell
  • Gauge and absolute measuring ranges 1 to 60 bar (15 to 1000 psi)
  • For general applications

The SITRANS P200 pressure transmitter for gauge and absolute pressure is used in the following industrial areas:

  • Mechanical engineering
  • Shipbuilding
  • Power engineering
  • Chemical industry
  • Water supply
  • High measuring accuracy
  • Rugged stainless steel enclosure
  • High overload withstand capability
  • For aggressive and non-aggressive media
  • For measuring the pressure of liquids, gases and vapors
  • Compact design

Application

 

Gauge and absolute pressure measurement

Liquids, gases and vapors

Mode of operation

 

Measuring principle

Piezo-resistive measuring cell (ceramic diaphragm)

Measured variable

Gauge and absolute pressure

Input

 

Measuring range

 

  • Gauge pressure
    • Metric
    • US measuring range

1 … 60 bar g (15 … 870 psi g)

15 … 1000 psi g

  • Absolute pressure
    • Metric
    • US measuring range

0.6 … 16 bar a (10 … 232 psi a)

10 … 300 psi a

Output

 

Current signal

4 ... 20 mA

  • Load

(UB - 10 V) / 0.02 A

  • Auxiliary power UB

7 ... 33 V DC (10 ... 30 V for Ex)

Voltage signal

0 ... 10 V DC

  • Load

≥ 10 kΩ

  • Auxiliary power UB

12 ... 33 V DC

  • Current consumption

< 7 mA at 10 kΩ

Characteristic curve

Linear rising

Measuring accuracy

 

Error in measurement at limit setting incl. hysteresis and reproducibility

  • Typical: 0.25 % of full-scale value
  • Maximum: 0.5 % of full-scale value

Step response time T99

< 5 ms

Long-term stability

 

  • Lower range value and measuring span

0.25 % of full-scale value/year

Influence of ambient temperature

 

  • Lower range value and measuring span

0.25 %/10 K of full-scale value

  • Influence of vibration (per IEC 60068-2-6)

0.005 %/g to 500 Hz in all directions

  • Influence of power supply

0.005 %/V

Rated conditions

 

Pressure transmitter with gasket made of:

 

  • FPM (Standard)

-15 ... +125 °C (5 ... 257 °F)

  • Neoprene

-35 ... +100 °C (-31 ... +212 °F)

  • Perbunan

-20 ... +100 °C (-4 ... +212 °F)

  • EPDM

-40 ... +145 °C (-40 ... +293 °F), usable for drinking water

Ambient temperature

-25 ... +85 °C (-13 ... +185 °F)

Storage temperature

-50 ... +100 °C (-58 ... +212 °F)

Degree of protection (to EN 60529)

  • IP 65 with connector per EN 175301-803-A
  • IP 67 with M12 connector
  • IP 67 with cable
  • IP 67 with cable quick screw connection

Electromagnetic Compatibility

  • Acc. to EN 61326-1/-2/-3
  • according to NAMUR NE21 for ATEX devices only, and with a max. measurement error of ≤ 1 %

Design

 

Weight

Approx. 0.090 kg (0.198 lb)

Process connections

See dimension drawings

Electrical connections

  • Connector per EN 175301-803-A Form A with cable inlet M16x1.5 or ½-14 NPT or Pg 11
  • M12 connector
  • 2 or 3-wire (0.5 mm2) cable (∅ ± 5.4 mm)
  • Cable quick screw connection

Wetted parts materials

 

  • Measuring cell

AI2O3 - 96 %

  • Process connection

Stainless steel, mat. no. 1.4404 (SST 316 L)

  • Gasket
  • FPM
  • Neoprene
  • Perbunan
  • EPDM

Non-wetted parts materials

 

  • Enclosure

Stainless steel, mat. no. 1.4404 (SST 316 L)

  • Rack

Plastic

  • Cable

PVC

Certificates and approvals

 

Classification according to pressure equipment directive (PED 97/23/EC)

For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice)

Lloyds Register of Shipping (LR)

Applied

Germanischer Lloyds Register of Shipping (GL)

Applied

American Bureau of Shipping (ABS)

Applied

Bureau Veritas (BV)

Applied

Det Norske Veritas (DNV)

Applied

Drinking water approval (ACS)

Applied

GOST

Applied

Explosion protection

 

Intrinsic safety "i" (only with current output)

Ex II 1/2 G Ex ia IIC T4 GA/gb

Ex II 1/2 D Ex ia IIIC T125 °C Da/Db

EC type-examination certificate

SEV 10 ATEX 0146

Connection to certified intrinsically-safe resistive circuits with maximum values

Ui ≤ 30 V DC; Ii = 100 mA; Pi ≤ 0.75 W

Effective internal inductance and capacity for versions with plugs per EN 175301-803-A and M12

Li = 0 nH; Ci = 0 nF


Device structure without explosion protection

The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure. It can be used with a connector per EN 175301-803-A (IP65), a round plug M12 (IP67), a cable (IP67) or a cable quick screw connection (IP67) connected electrically. The output signal is between 4 and 20 mA or 0 and 10 V.

Device structure with explosion protection

The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure. It can be used with a connector per EN 175301-803-A (IP65) or a round plug M12 (IP67) connected electrically. The output signal is between 4 and 20 mA.

The pressure transmitter measures the gauge and absolute pressure as well as the level of liquids and gases.

Mode of operation

SITRANS P200 pressure transmitters (7MF1565-...), functional diagram

The ceramic measuring cell has a thin-film resistance bridge to which the operating pressure p is transmitted through a ceramic diaphragm.

The voltage output from the measuring cell is converted by an amplifier into an output current of 4 to 20 mA or an output voltage of 0 to 10 V DC.

The output current and voltage are linearly proportional to the input pressure.

SITRANS P200, electrical connections, dimensions in mm (inch)

SITRANS P200, process connections, dimensions in mm (inch)

Connection with current output and connector per EN 175301

Connection with current output and connector M12x1

Connection with current output and cable

Connection with current output and cable quick screw connection

Connection with voltage output and connector per EN 175301

Connection with voltage output and connector M12x1

Connection with voltage output and cable

Connection with voltage output and cable quick screw connection

Version with explosion protection: 4 ... 20 mA

The grounding connection is conductively bonded to the transmitter enclosure

Connection with current output and connector per EN 175301 (Ex)

Connection with current output and connector M12x1 (Ex)

  • Описание : sitrans p200 transmitters for pressure and absolute pressure for general applications non-linearity: 0,25 percent (typically) wetted parts material:ceramics, stainless steel plus sealing material; non-wetted parts material: stainless steel
  • Вес (кг) : 0.2
Код Заказной номер Заказать
71415 7MF1565-.....-.... Заказать
;