;

ION SIMATIC S7 PN производства Siemens

  • Function block for data acquisition from a SIMATIC S7-300/400 PLC with PROFINET CPU
  • For provision of measured data for further processing with SIPLUS CMS4000 X-Tools
  • Integrated into the user program of the PLC
  • Cyclic data transfer of measured data to the higher-level industrial PC over Ethernet
  • Processing of communication via integral PROFINET interface of the CPU

The ION SIMATIC S7 PN allows numeric data to be read out cyclically from a SIMATIC S7-300/400 PLC and transferred to an industrial PC containing the SIPLUS CMS4000 X-Tools analysis software. The CPU of the PLC must have an integral PROFINET interface.

The ION SIMATIC S7 PN function block is integrated in the user program of the SIMATIC S7-300/400.

The Ethernet connection required for data transmission is established via the integral PROFINET interface of the CPU.

The SIPLUS CMS4000 X-Tools analysis software is installed on the higher-level evaluation PC.

The data to be acquired from the SIMATIC S7-300/400 is selected by configuring the ION SIMATIC S7 PN function block in the SIMATIC S7.

The function block is initialized in the startup OB of the PLC (OB100, OB101, OB102). For this purpose, the COM_RST parameter is set to TRUE. During initialization, the number of active channels is determined, the cycle time imported, and further calculations made for operation. The channels are filled with data in the program of the S7.

The FB is then executed passively in the program. Data exchange with the analysis software on the industrial PC only starts after being called in a time interrupt OB (e.g. OB35) by SIPLUS CMS4000 X-Tools. The data is visualized, analyzed and archived there.

The signals are collected in two buffers for the transmission and then sent to X-Tools with relative time tags. Each buffer can accommodate 712 bytes. With 178 active channels, one buffer serves as a send buffer, and the current values are written in the other. The buffers are read and sent alternately. If not all of the channels are activated, several cycles can be buffered:
With 89 channels, one buffer can save two cycles, and a send job is therefore only initiated after two cycles. The communication load is thus reduced.

From the point of view of X-Tools, the ION SIMATIC S7-400 T001 appears as an Ethernet device which communicates by means of UDP/IP.

The use of an ION SIMATIC S7 PN function block enables transmission of max. 178 channels per recording cycle of the controller. This corresponds to a data volume of 712 bytes. If this volume is insufficient or if the cycle time is very small, several function blocks can be used in the user program.

The number of channels and their content can be freely configured and combine several signals (e.g. 1 word signal and 16 bit signals).

More information or product details can be obtained from

  • Вес (кг) : 0.3
Код Заказной номер Описание Заказать
60836 6AT8000-0AB00-1BA0 castomat - software x-tools standard v 03.00; process data simulation; process data storage; process data visualisation; process data evaluation; Заказать
109248 6AT8000-0AB00-2BA0 castomat - software x-tools professional v 03.00; process data simulation; process data storage; process data visualisation; process data evaluation; server-client coupling Заказать
60840 6AT8000-0CA00-4XA0 castomat - software ion simatic s7-400 t002 aquisition of numerical data software- interface; ethernet cpu 41x with cp443-1 Заказать
;