The LA724ISSR is the high-current power output module for controlling external SSR solid-state relays (up to 90 A/load).

LA724I SSR power output module

Outputs per power output module

24

Galvanic isolation from control unit

By means of optocouplers specified according to EN 60747-5-2

Insulation voltage of the optocouplers

5.3 kV

Galvanic isolation of diagnostic inputs from each other

no

Diagnosis voltage (for star and delta connection)

 

  • Rated value

230/400 V AC

  • Permissible range

187 ... 264 V/340 ... 460 V AC

  • Frequency

50/60 Hz (47 ... 63 Hz)

Total current per phase and module

See SM724I current measuring module

Current per busbar, max.

120 A

24 V supply voltage for controlling the solid state relays SSR

 

  • Rated value

24 V

  • Permissible range

20.4 ... 28.8 V

  • Fuse protection

1.5 A/250 V quick-response (external)

Control voltage

24 V

  • At rated supply voltage

Typ. 23.3 V
min. 22 V

Max. control current

50 mA per control output

Max. cable length

 

  • Control cable to solid state relay SSR

30 m

  • Connection cable to SM724I current measuring module

30 m

  • 24 V supply voltage

10 m

Note:

Cables not to be laid outside buildings

Dimensions (W x H x D)

50 mm x 480 mm x 210 mm

Weight

Approx. 3.3 kg


  • Connection of the 24 V supply voltage
  • Connection of the solid state relay via mating connector
  • Connection of the external SM724I current measuring module
  • Connection of voltage feedbacks from the load circuits
  • Connection of phases L1, L2, L3 and the neutral conductor via busbars
    (only required with voltage diagnostics)
Output data
  • 24 channels with a digital control signal 24 V (8 outputs per phase)
  • Max. 20 kW switching capacity at 230 V or 36 kW at 400 V per output
Supply voltage monitoring

The connected 24 V supply is monitored for failure. In the event of failure, the outputs to the solid state relay (SSR) are deactivated.

The drivers of the control outputs are monitored for their function.

Fuses

Fuses are to be set externally for each channel.

Diagnostics facilities

Two alternative diagnostic methods are possible:

  • By diagnosing the voltages from the load circuit, the following faults can be detected:
    • Solid state relay (SSR) cannot be activated, supply line to the SSR is interrupted or external channel fuse has failed
    • The solid state relay (SSR) cannot be deactivated; emitter or cable break
  • By diagnosing via the external SM724I current measuring module, the following faults can additionally be detected:
    • Rated output on channel is exceeded
    • Rated output on channel is not reached

This diagnosis is recommended for detecting faults in emitters connected in parallel.

Design

Type

Mating connectors

 
  • for the 24 V power supply

A5E00210675

  • for connection of the solid state relay (SSR)
    (3 units required per power output module)

A5E00043661

  • for connection of the SM724I current measuring module

A5E00210670

  • for voltage diagnostics
    (3 units required for each power output module)

41818384


Recommendation for solid state relay (SSR) to be used

SIRIUS SC semiconductor relay/contactor, e.g. 3RF2350‑1AA02:
semiconductor contactor 50 A, 40 °C, control voltage 24 V, screw-type connection

Код Заказной номер Описание Вес (кг) Заказать
110020 6BK1700-2BA10-0AA0 la 724 управление нагревом силовой выход на центр. сх. za 724 ssr-версия 3.5 Заказать
110502 6ES7171-2XX00-6DA0 управление нагревом-токовые шины как зап. часть 0.022 Заказать
;