Control Module производства Siemens

Control Module

The SINAMICS DC MASTER Control Module is mainly used for retrofitting and modernizing DC drives in existing plants and systems. In DC technology, there are many anterior plants and systems that cannot be connected to modern automation systems.

When such plants and systems are retrofitted or upgraded, the motor, mechanical system and power section are retained and only the closed-loop control section is replaced by a Control Module. As a consequence, an extremely favorably-priced modern DC drive is obtained with the full functional scope of the well-proven, fully digital units from the SINAMICS DC MASTER series.

The new system is adapted to the configuration of the existing components using simple parameterization.

The SINAMICS DC MASTER Control Module contains a power section for the field supply with a rated current of 40 A.

For general technical data, see section "DC Converters"

 

 

Type

 

 

6RA8000-0MV62-0AA0

Rated armature supply voltage that can be sensed

V

50/125/250/575/1 000

Rated supply voltage, electronics power supply

V

24 DC (18 … 30 V DC); In = 5 A

Rated field supply voltage 1)

V

480 V 2 AC (+10/-20 %)

Rated frequency

Hz

45 … 65

Rated DC field voltage 1)

V

Max. 390

Rated DC field current

A

40

Normal ambient temperature in operation

°C

0 … +55

Dimensions

  
  • Width

mm

271

  • Height

mm

388

  • Depth

mm

253

Weight, approx.

kg

12


1) The field supply voltage can lie below the rated field voltage (set using a parameter, input voltages of up to 85 V are permissible). The output voltage decreases accordingly. The specified DC output voltage can be reliably provided up to a 5 % undervoltage of the line supply voltage (rated field supply voltage).

The SINAMICS DC MASTER Control Module sets itself apart as a result of its compact, space-saving design. The compact design where all of the individual components are easily accessible offers a high degree of service friendliness.

In order to be able to optimally use the mounting and installation possibilities in the plant or system, the SINAMICS DC MASTER Control Module can be split depthwise. In addition, the PC boards for generating and distributing the firing pulses as well as for the fuse monitoring and voltage sensing can be implemented so that they can be mounted outside the unit close to the power section.

Alternatively, when commissioning the drive system with STARTER, the adaptations, settings and measured value displays required can be made using the Basic Operator Panel BOP20 or the Advanced Operator Panel AOP30.

The AOP30 offers a favorably-priced alternative to measuring equipment installed in the electrical cabinet.

The field is supplied from a single-phase, half-controlled bridge circuit B2HZ. The field power section is implemented using electrically insulated thyristor modules, which means that the heatsink is floating.

Note:
When ordering a unit with options, add the suffix “-Z” after the Order No. and then state the order code(s) for the desired option(s) after the suffix.

Examle:
6RA8000-0MV62-0AA0-Z
G00+G20+L10+...

Available options

The following table provides an overview of the available options. Detailed descriptions of the options are provided in the section “Description of options”.

   

Order No. for separate order

Designation

Order code

Notes

not coated

coated

CUD

Standard CUD left

(Standard)

6RY1803‑0AA00

6RY1803‑0AA20

Advanced CUD left

G00

6RY1803‑0AA05

6RY1803‑0AA25

Standard CUD right

G10

This option requires an Advanced CUD left – order code G00

6RY1803‑0AA00

6RY1803‑0AA20

Advanced CUD right

G11

This option requires an Advanced CUD left – order code G00

6RY1803‑0AA05

6RY1803‑0AA25

Communication Board CBE20 left

G20

This option requires an Advanced CUD left – order code G00

6SL3055-0AA00-2EB0

Communication Board CBE20 right

G21

This option requires an Advanced CUD right – order code G11

6SL3055-0AA00-2EB0

Memory card left

S01

6RX1800-0AS01

Memory card right

S02

This option requires a Standard CUD right – order code G10 – or an Advanced CUD right – order code G11

6RX1800-0AS01

Field

Field power section 1Q

(Standard)

– 1)

– 1)

Field power section 2Q

L11

– 1)

– 1)

Without field power section

L10

Additional options

Coated PCBs

M08

Nickel-plated copper busbars

M10


1) Available as spare part.

The SINAMICS DC MASTER Control Module can be split up into several individual modules. These can be mounted separately from one another.

Optional, pre-fabricated cable sets are available to connect the individual modules.

This means that the drive system can be quickly but also flexibly adapted to the plant or system configuration.

Description

Content

Connection

Order No.

Rear enclosure part including accessories for mounting the firing pulse transformer module and/or fuse monitoring module for a parallel connection

Set of loose parts

 

6RY1805‑0CM00

Screws, stud bolts, and snap-on parts to externally mount module parts

Set of loose parts

 

6RY1807‑0CM00

Pre-fabricated connection set
ribbon cable:
To connect the two cradles when separately mounted

2 x 26-core ribbon cable
shielded (3 m long)

from X21A, X22A on PC board -A7109-
to X21A, X22A on PC board -A7043-

6RY1707‑0CM01

1 x 10-core ribbon cable
shielded (3 m long)

from X23B on PC board -A7109-
to X23B on PC board -A7118-

1 x 20-core ribbon cable
shielded (3 m long)

from XF1 on PC board -A7109-
to XF1 on PC board -A7116-

1 x RJ45 patch cable
shielded (3 m long)

from X45 on PC board -A7109-
to X45 on PC board -A7117-

Pre-fabricated connection set
ribbon cable:
To connect the two cradles when separately mounted

2 x 26-core ribbon cable
shielded (10 m long)

from X21A, X22A on PC board -A7109-
to X21A, X22A on PC board -A7043-

6RY1807‑0CM02

1 x 10-core ribbon cable
shielded (10 m long)

from X23B on PC board -A7109-
to X23B on PC board -A7118-

1 x 20-core ribbon cable
shielded (10 m long)

from XF1 on PC board -A7109-
to XF1 on PC board -A7116-

1 x RJ45 patch cable
shielded (10 m long)

from X45 on PC board -A7109-
to X45 on PC board -A7117-

Pre-fabricated connection set for
current transformer

2 x 2-core twisted cable
(2 m long)

from XB on PC board -A7109-
to the current transformers

6RY1707‑0CM03 1)

Pre-fabricated connection set for
current transformer

2 x 2-core cable
shielded (10 m long)

from XB on PC board -A7109-
to the current transformers

6RY1707‑0CM04 1)

Pre-fabricated connection set for
heatsink temperature sensing

1 x 2-core cable
shielded (10 m long)

from XT6 on PC board -A7109-
to temperature sensor on the heat sink

6RY1707‑0CM05

Pre-fabricated connection set for
firing pulse cables

Connection set for 12 x 2-core twisted cable (3 m long)

from XIMP11, XIMP12, XIMP13, XIMP14, XIMP15, XIMP16, XIMP21, XIMP22, XIMP23, XIMP24, XIMP25,
XIMP26 to the thyristors

6RY1707‑0CM06 1)

Pre-fabricated connection set for
fuse monitoring

6 x 2-core twisted cable (10 m long)

from XS1_5, XS2_5, XS3_5, XS4_5, XS5_5, XS6_5, XS7_5, XS8_5, XS9_5, XS10_5, XS11_5, XS12_5
or XS1_4, XS2_4, XS3_4, XS4_4, XS5_4, XS6_4, XS7_4, XS8_4, XS9_4, XS10_4, XS11_4, XS12_4
or XS1_3, XS2_3, XS3_3,
XS4_3, XS5_3, XS6_3, XS7_3, XS8_3, XS9_3, XS10

6RY1807‑0CM07

Pre-fabricated connection set for
voltage sensing

1 x 3-core twisted cable
U-V-W (3 m long)
1 x 2-core twisted cable
C-D (3 m long)

from XU6, XV6, XW6 or XU5, XV5, XW5 or XU4, XV4, XW4 or XU3, XV3, XW3 or XU2, XV2, XW2 or
XU1, XV1, XW1 depending on the voltage
(5,6 V, 50 V, 125 V, 250 V, 575 V or 1000 V) to supply XC6, XD6 or XC5, XD5 or XC4, XD4 or XC3, XD3 or XC2, XD2

6RY1807‑0CM08

Pre-fabricated connection set for
controlling the firing pulse transformers

12 x 2-core twisted cable
(1 m long)

from XIMP1, XIMP4 or XIMP2, XIMP5 or XIMP3, XIMP6 on PC board
-A7043- (side parts) on the
firing pulse transformer modules (single boards) with the terminals
X11, X12, X13, X14, X15, X16, X21, X22, X23, X24, X25, X26

6RY1707‑0CM13 1)

Pre-fabricated connection set for
controlling the firing pulse transformers

2 x 12-core cable
shielded (10 m long)

from XIMP1, XIMP4 and/or XIMP2, XIMP5 and/or XIMP3, XIMP6 on PC board -A7043- to the external firing pulse transformers

6RY1707‑0CM10 1)

Pre-fabricated connection set for
mounting cradles next to each other

2 x 26-core ribbon cable
shielded (10 m long)

from X21A, X22A on PC board -A7109-
to X21A, X22A on PC board -A7043-

6RY1807‑0CM11

1 x 10-core ribbon cable
shielded (10 m long)

from X23B on PC board -A7109-
to X23B on PC board -A7118-

1 x 20-core ribbon cable
shielded (10 m long)

from XF1 on PC board -A7109-
to XF1 on PC board -A7116-

1 x RJ45 patch cable
shielded (10 m long)

from X45 on PC board -A7109-
to X45 on PC board -A7117-


1) Unchanged when compared to the SIMOREG DC-MASTER Control Modules.

Код Заказной номер Описание Вес (кг) Заказать
66748 6RA8000-0MV62-0AA0 sinamics dcm control module without power section incl 40a controllable field rectifier 12 Заказать
115055 6RY1707-0CM01 набор проводов (ленточный кабель): состав: 2 экранированных ленточных кабеля 26-жил (длина=3m) 2 экранированных ленточных кабеля 10-жил (длина=3m) 1 экранированный ленточный кабель 20-жил (длина=3m) 0.79 Заказать
115057 6RY1707-0CM03 набор проводов для трансформаторов тока состав: 2 одножильные витые пары (длина=2m) 0.12 Заказать
66964 6RY1707-0CM04 набор проводов для трансформаторов тока: состав: 2 экранированных двухпроводных кабеля (длина=10m) 0.3 Заказать
115058 6RY1707-0CM05 набор проводов для контроля температуры радиатора: состав: 1 экранированный двухпроводный кабель (длина=10m) 0.3 Заказать
66965 6RY1707-0CM06 набор проводов для d151: состав: 12 одножильных витых пар (устойчивые к короткому замыканию провода) (длина=3m) 0.62 Заказать
115059 6RY1707-0CM10 набор проводов для импульсный трансформатор для управления силовыми модулями: состав: 2 экранированных кабеля 12-жил (длина=10m) 1.85 Заказать
66968 6RY1707-0CM13 набор проводов для импульсного трансформатора для управления силовыми модулями: состав: 12 одножильных витых пар (длина=1m) 0.3 Заказать
115121 6RY1805-0CM00 housing for control module 5 Заказать
115128 6RY1807-0CM00 set of loose parts (required for external use of printed curcuit boards) 1 Заказать
115129 6RY1807-0CM02 set of wires: 2 pieces x ribbon cable shielded 26-way (length=10m) 1 piece x ribbon cable shielded 10-way (length=10m) 1 piece x ribbon cable shielded 20-way (length=10m) 1 piece x rj45 patchcable shielded (length=10m) 1.2 Заказать
67038 6RY1807-0CM07 set of wires for fuse control contents: shielded 26-way (length=3m) 6 pieces single wires (short-circuit-proof cables) twisted pairs (length=10m) 0.45 Заказать
67039 6RY1807-0CM08 set of wires for voltage measurement: content. 1 piece x single wires (short-circuit-proof cables) u-v-w twisted (length=3m) 1 piece single wires (short-circuit-proof cables) c-d twisted (length=3m) 0.9 Заказать
115131 6RY1807-0CM11 set of wires: 2 pieces x ribbon cable 26-way (length=1m) 1 piece x ribbon cable 10-way (length=1m) 1 piece x ribbon cable 20-way (length=1m) 1 piece x rj45 patchcable shielded (length=1m) 1.3 Заказать
;