Note:
A general introduction to WirelessHART and information on the WirelessHART adapter and the WirelessHART field devices can be found in Catalog FI 01 or on the Internet at http://www.siemens.com/wirelesshart
The IE/WSN-PA LINK connects wireless HART field devices by radio to the Ethernet. On the radio side, the IE/WSN-PA LINK supports the WirelessHART standard and on the Ethernet side the TCP/IP and Modbus TCP communication.
The IE/WSN-PA LINK thus enables wireless diagnostics, maintenance and process monitoring.
Monitoring
WirelessHART is particularly suitable for use in plant sections that are to be included in monitoring, but which do not have any existing MSR cabling, e.g. external tank stores or other installations where high cabling costs are anticipated. Data for the visualization can be retrieved from the IE/WSN-PA link via Industrial Ethernet or Modbus TCP.
Monitoring of process states via WirelessHART
Retrofitting for diagnostics and maintenance
For this application, wireless adapters are looped into the 4-20 mA interface or screwed directly onto the HART device. The acyclic HART message frames are transmitted by radio between IE/WSN-PA LINK and a wireless adapter. Without affecting the operation of the plant, the wireless adapter modulates the acyclic HART message frames to the 4-20 mA interface or extracts them from the 4-20 mA interface.
The IE/WSN-PA LINK collects the data of all wireless adapters and transfers it via Industrial Ethernet to the diagnostics and maintenance station.
If greater distances between the IE/WSN-PA LINK and the monitoring station are to be spanned without cabling, this can be implemented by means of Industrial Wireless LAN with the access points and client modules of the SCALANCE W family.
Retrofitting of plants for diagnostics and maintenance
Product versions
WirelessHART
The IE/WSN-PA LINK establishes on the radio side an intermeshed wireless sensor network for communication with wireless field devices (e.g. transmitters). The data from the wireless field devices is received by the IE/WSN-PA LINK and transmitted via Industrial Ethernet to the connected systems. The supported wireless network is an open wireless network specified by the HART Communication Foundation (HCF) in accordance with the WirelessHART (HART V7.1) standard.
On the field device side, the IE/WSN-PA LINK requires field devices that support WirelessHART (HART). Existing field devices can be integrated by means of wireless adapters into the WirelessHART communication. To this end, the adapters are looped into the 4-20 mA interface. In addition, as many as four standard HART field devices with external power supply can be connected to the adapter in multidrop mode. Individually connected devices can be operated with the battery of the adapter.
The adapter wirelessly transmits all data and process values of the connected devices. The advantage of this solution is that tried and tested devices can continue to be used.
Industrial Ethernet
Via the Ethernet interface the IE/WSN-PA LINK supports the use of the HART OPC server and the Modbus TCP protocol.
Configuration
The configuration is web-based, without additional software, and performed from the PC. By means of the web user interface it is also possible to display the device states and measured values of the WirelessHART devices.
Integration into automation systems
The IE/WSN-PA LINK can be integrated into automation systems via Ethernet or Modbus TCP. Communication modules (CP 343-1 or CP 443-1) are required to connect the IE/WSN-PA LINK to SIMATIC S7-300/400. Function blocks and technical support can be found at:
www.siemens.com/simatic-net/ik-info
Integration in PCS 7
For integration of the IE/WSN-PA LINK into PCS 7 you can obtain function blocks and technical support at:
Bestell-Nr. | 6GK1 411-6CA40-0AA0 | 6GK1 411-6CA40-0BA0 |
Product type designation | IE/WSN-PA LINK | IE/WSN-PA LINK |
Data transmission rate |
|
|
| 10 … 100 Mbit/s | 10 … 100 Mbit/s |
| 10 … 100 Mbit/s | 10 … 100 Mbit/s |
| 9.6 to 57.6 kbps | 9.6 to 57.6 kbps |
Interfaces |
|
|
Number of electrical connections |
|
|
| 1 | 1 |
| 1 | 1 |
| 1 | 1 |
| 1 | 1 |
Design of electrical connection |
|
|
| RJ 45 port | RJ 45 port |
| RJ 45 port | RJ 45 port |
| 2-pin terminal strip | 2-pin terminal strip |
| 3-pin terminal strip | 3-pin terminal strip |
Interfaces Wireless |
|
|
Number of radio cards permanently installed | 1 | 1 |
Number of internal antennas | 1 | 0 |
Number of electrical connections for external antenna(s) | 0 | 1 |
Design of electrical connection for external antenna(s) | - | N-Connector |
Supply voltage, current consumption, power loss |
|
|
Type of power supply | DC | DC |
Supply voltage, external | 24 V | 24 V |
| 20 V | 20 V |
| 28 V | 28 V |
Current consumed from external power supply at 24 V DC, maximum | 0.5 A | 0.5 A |
Effective power loss, maximum | 12 W | 12 W |
Permitted ambient conditions |
|
|
Ambient temperature |
|
|
| -40 … +60 °C | -40 … +60 °C |
| -40 … +85 °C | -40 … +85 °C |
| -40 … +85 °C | -40 … +85 °C |
Relative humidity at 25 °C without condensation during operating phase, maximum | 90 % | 90 % |
IP degree of protection | IP 65 | IP 65 |
Design, dimensions and weights |
|
|
Housing width | 229 mm | 229 mm |
Housing height |
|
|
| 306 mm | 306 mm |
| 354 mm | 354 mm |
Housing depth | 89 mm | 89 mm |
Net weight | 4.54 kg | 4.54 kg |
Type of mounting |
|
|
| Yes | Yes |
| Yes | Yes |
Type of mounting | Material for mast mounting included in scope of delivery | Material for mast mounting included in scope of delivery |
Radio frequencies |
|
|
Radio frequency with WirelessHART in the 2.4 GHz frequency band |
|
|
| 2.4 GHz | 2.4 GHz |
| 2.5 GHz | 2.5 GHz |
Performance data WirelessHART |
|
|
Number of WirelessHART devices which can be operated | 100 | 100 |
Network latency |
|
|
| 10 s | 10 s |
| 5 s | 5 s |
Transition link between two devices with WirelessHART network |
|
|
| 100 m | 100 m |
| The values may deviate if obstacles affecting radio transmission are present | The values may deviate if obstacles affecting radio transmission are present |
HART protocol is supported | Yes | Yes |
Product properties, functions, components General |
|
|
Protocol is supported |
|
|
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Product functions Management, configuration, programming |
|
|
Product function |
|
|
| Yes | Yes |
| Yes | Yes |
Product functions Diagnostics |
|
|
Product function |
|
|
| Yes | Yes |
| Yes | Yes |
Product functions Security |
|
|
Product function |
|
|
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
SSL protocol is supported | Yes | Yes |
Encryption principle | AES 128 bit | AES 128 bit |
Product functions Time |
|
|
NTP protocol is supported | Yes | Yes |
Standards, specifications, approvals |
|
|
Standard for WirelessHART | HART V 7.1 | HART V 7.1 |
Standard for wireless communication IEEE 802.15.4 | Yes | Yes |
Certificate of suitability |
|
|
| Yes | Yes |
| CSA Division 2 & Dust Ignition-proof for Class I, Division 2, Groups A, B, C, and D. Dust Ignition-proof for Class II, Groups E, F, and G / Suitable for Class III Hazardous Locations. / Install per Siemens drawing A5E02467236A. Temperature Code: T4 (-40°C < Ta < 60°C) CSA Enclosure Type 4X | CSA Division 2 & Dust Ignition-proof for Class I, Division 2, Groups A, B, C, and D. Dust Ignition-proof for Class II, Groups E, F, and G / Suitable for Class III Hazardous Locations. / Install per Siemens drawing A5E02467236A. Temperature Code: T4 (-40°C < Ta < 60°C) CSA Enclosure Type 4X |
| FM Division 2, Non-Incendive for Class I, Division 2, Groups A, B, C, and D. Dust Ignition-proof for Class II, III, Division 1, Groups E, F, and G / Indoor and outdoor locations / NEMA Type 4X Temperature Code: T4 (-40°C < Ta < 60°C) | FM Division 2, Non-Incendive for Class I, Division 2, Groups A, B, C, and D. Dust Ignition-proof for Class II, III, Division 1, Groups E, F, and G / Indoor and outdoor locations / NEMA Type 4X Temperature Code: T4 (-40°C < Ta < 60°C) |
| ATEX type n, see note: Certificate number: Baseefa10ATEX0044X, ATEX marking: Ex II 3 G, Ex nA nL IIC T4 (-40 °C <= Ta <= 60 °C), rated voltage: 28 V, ATEX Dust Ignition-proof: Certificate number: Baseefa10ATEX0045X, ATEX marking: II 3 D, Ex tD A22 IP66 T135 (-40 °C <= Ta <= 60 °C), rated voltage: 28 V. Note on type n: Conditions for safe handling during installation: The device does not pass the 500 V insulation test in accordance with paragraph 6.8.1 of EN 60079-15:2005. This must be taken into account when installing the device. | ATEX type n, see note: Certificate number: Baseefa10ATEX0044X, ATEX marking: Ex II 3 G, Ex nA nL IIC T4 (-40 °C <= Ta <= 60 °C), rated voltage: 28 V, ATEX Dust Ignition-proof: Certificate number: Baseefa10ATEX0045X, ATEX marking: II 3 D, Ex tD A22 IP66 T135 (-40 °C <= Ta <= 60 °C), rated voltage: 28 V. Note on type n: Conditions for safe handling during installation: The device does not pass the 500 V insulation test in accordance with paragraph 6.8.1 of EN 60079-15:2005. This must be taken into account when installing the device. |
| IECEx type n, see note: Certificate number: IECEx BAS 10.0014X, Ex nA nL IIC T4 (-40 °C <= Ta <= 60 °C), rated voltage: 28 V, IECEx Dust Ignition-proof, see note: Certificate number: IECEx BAS 10.0015X, Ex tD A22 IP66 T135 (-40 °C <= Ta <= 60 °C), rated voltage: 28 V. Note on type n: Conditions for safe handling during installation: The device does not pass the 500 V insulation test in accordance with paragraph 6.8.1 of EN 60079-15:2005. This must be taken into account when installing the device. | IECEx type n, see note: Certificate number: IECEx BAS 10.0014X, Ex nA nL IIC T4 (-40 °C <= Ta <= 60 °C), rated voltage: 28 V, IECEx Dust Ignition-proof, see note: Certificate number: IECEx BAS 10.0015X, Ex tD A22 IP66 T135 (-40 °C <= Ta <= 60 °C), rated voltage: 28 V. Note on type n: Conditions for safe handling during installation: The device does not pass the 500 V insulation test in accordance with paragraph 6.8.1 of EN 60079-15:2005. This must be taken into account when installing the device. |
| - | - |
Wireless approval | FCC and IC approval | IC approval |
Current approvals can be found on the Internet at:
Код | Заказной номер | Описание | Вес (кг) | Заказать |
---|---|---|---|---|
114340 | 6GK1411-6CA40-0AA0 | ie/wsn-pa link with integrated antenna; network transition between wireless hart and ethernet; ethernet 10/100 mbit/s; tcp/ip, modus tcp; wireless hart with 2.4 ghz; national approval usa, canada, europe,ex-certification zone 2; rs 485 with modbus rtu | 4.54 | Заказать |
66299 | 6GK1411-6CA40-0BA0 | simatic net,ie/wsn-pa link for external antenna connect.; network transition between wireless hart and ethernet; ethernet 10/100 mbit/s; tcp/ip, modus tcp; wireless hart with 2.4 ghz; national approval europe; ex-certfication zone 2; rs 485 with modbus rtu | 4.54 | Заказать |
114448 | 6GK1901-0DB20-6AA0 | simatic net ie fc m12 plug pro, m12 втычной коннектор в металлическом корпусе, с быстрым подключением с осевым отводом кабеля (d coded), 1 пакет = 1 шт., для scalance x208 pro и et200 pro pn | 0.04 | Заказать |
114576 | 6GK5792-6MN00-0AA6 | simatic net, iwlan антенна ant 792-6mn с всенаправленной характеристикой, коэффициент усиления, включая n-розетку: 6 dbi ip65 (-20-+60град. цельс.), 2.4 ghz wi-fi совместимость и национальные разрешения, монтаж на мачте или стене, компактное печатное руководство на нем./англ. входит в объём поставки | 1 | Заказать |
66537 | 6GK5795-6MN00-0AA6 | simatic net, iwlan antenna ant 795-6mn со всенаправленной характеристикой, коэффициент усиления включая n-розетку: 6/8 dbi ip65 (-20-+60град. цельс.), 2.4/5ghz wi-fi совместимость и национальные разрешения, монтаж на крыше или транспортном средстве, компактное печатное руководство на нем./англ. входит в объём поставки | 1 | Заказать |
114580 | 6GK5795-6MN01-0AA6 | simatic net, iwlan монтажное приспособление для антенн (ant 795-6mn), для монтажа антенны ant795-6mn на крышу, ip20, (-20-+60град. цельс.), компактное печатное руководство на нем./англ. входит в объём поставки | 1 | Заказать |
114584 | 6GK5798-0CP00-1AA0 | simatic net, iwlan rcoax n-подключение соединитель вилка/ вилка 2,4ггц устройство соединения | 0.06 | Заказать |
66542 | 6GK5798-2LP00-2AA6 | simatic net, iwlan грозозащита lp 798-1n с подключением n/n вилкой/розеткой для антенн ant 790, ip65 (-40-+100 град. цельсия), компактное печатное руководство на нем./англ. входит в объём поставки | 0.104 | Заказать |
70514 | 6XV1840-2AH10 | simatic net, fc стандартный ie tp кабель для быстрого монтажа (fc), для подкл. к fc соединителю rj45, 4-жильный, экранированный, категория 5, поставка по метражу отрезками длиной 20 ... 1000 m | 0.068 | Заказать |
70636 | 6XV1875-5AH10 | simatic net, iwlan rcoax n-соединение вилка/ вилка гибкий соединительный кабель предсобранный, длина 1m 2,4ггц гибкий соединительный кабель для 2 rcoax сегментов | 0.141 | Заказать |
117105 | 6XV1875-5AH20 | simatic net, гибкий предсобранный коаксиальный кабель n-connect (две вилки) для сетей iwlan, длина 2m, 2.4 и 5 gгц, гибкий кабель для 2 сегментов rcoax | 0.221 | Заказать |
70637 | 6XV1875-5AH50 | simatic net, iwlan rcoax n-соединение вилка/ вилка гибкий соединительный кабель предсобранный, длина 5m 2,4ггц гибкий соединительный кабель для 2 rcoax сегментов | 0.439 | Заказать |
70638 | 6XV1875-5AN10 | simatic net, гибкий предсобранный коаксиальный кабель n-connect (две вилки) для сетей iwlan, длина 10m, 2.4 и 5 gгц, гибкий кабель для 2 сегментов rcoax | 0.847 | Заказать |