Input modules
3 different input modules are available in the HabiTEQ to connect external contacts such as solar/wind detector, movement detector, door switches, push-buttons and analogue sensors.
8/16 optical isolated inputs are provided, which must be potential-free.
The input contacts can be selected and set using the PC software:
• Push-button = button that is open when inactive (e.g. doorbell)
• Normal open = contact that is open when inactive
• Normal closed = contact that is closed when inactive
• Switch = single-pole conventional switch. The maximum length of each input is 200m. The cable type is irrelevant as long as the 2 wires are each 1mm2. (Contact load 1mA)
Each of the 8 inputs has two serial numbers. The common (fi rst connector on the right top and bottom) is connected internally. One may connect these together with other INP16 modules.